Main applications
- Building services
- Fire fighting and sprinkler systems
- Irrigation
- Pressure boosting, fire fighting systems
- Water supply
Technical data
- Q max 88.0 m³/h
- H max 134.0 m
Design ksb delta primo
Fully automatic package pressure booster system with two to three (VC) / four (F/SVP) vertical high-pressure pumps; available in cascade-controlled and two variable speed versions. Cascade control (F) for ensuring the required supply pressure. The frequency inverter operated VC and SVP versions ensure variable speed control of each pump via cabinet-mounted frequency inverter (VC) or PumpDrive variable speed system and KSB SuPremE motor (SVP), respectively, providing fully electronic control to ensure the required supply pressure. Automated with BoosterControl.
Application pump ksb delta primo
Pressure boosting in residential buildings, hospitals, office buildings, hotels, department stores, industry, etc.
Drive pump ksb delta primo
- KSB Delta Primo F, VC:
- Electric motor
- Efficiency class IE3 to IEC 60034-30
- KSB Delta Primo SVP:
- Magnetless synchronous reluctance motor
- Efficiency class IE5 to IEC 60034-30
- KSB SuPremE
Desing Details pump ksb delta primo
▪ Compact system mounted on a common base frame
▪ 2 (F / SVP / VC) / 3 (F / SVP / VC) / 4 (F / SVP) vertical highpressure pumps
▪ Hydraulic components made of stainless steel / brass
▪ Integrated dry running protection
KSB Delta Primo F:
▪ DOL starting
KSB Delta Primo VC, SVP:
▪ With variable speed system
Multiple pump system:
▪ Discharge-side gate valve per pump
For inlet conditions M and F only:
▪ Check valve per pump
▪ Suction-side gate valve per pump
KSB Delta Primo F:
▪ Power contactor per pump
KSB Delta Primo VC, SVP:
▪ One frequency inverter per pump
▪ Power contactor per pump
Overview of technical data ksb delta primo
Q (50Hz) | 0.2 – 88.0 (m³/h) |
H (50Hz) | 0.0 – 134.0 (m) |
Type of bearing | Plain bearings |
Drive frequency | 50 Hz |
Type of drive | Electric motor |
Drive voltage | Low voltage |
Type of installation | Long-coupled |
Type of coupling | Direct |
Type of lubrication | Grease / Product lubrication |
Max. permissible fluid temperature | 60.0 (°C) |
Pump set location | Dry installed |
Suitable for drinking water | Yes |
Type of impeller | Closed / Radial |
Minimum inlet pressure | 4.0 (bar) |
Installation position | Vertical |
Shaft seal type | Mechanical seal |
Main applications | Industry and process engineering, Water, Building services |
Casing material | Chrome nickel steel, Stainless steel |
Maximum discharge-side pressure | 16.0 (bar) |
Maximum drive rating | 7.5 (kW) |
Type of installation | Stationary |
Maximum speed of rotation | 2900.0 (1/min) |
Type of connection | Indirect |