Hya-Solo D FL
Hya-Solo D FL

Main applications Hya-Solo D FL

  • Main applications
  • Building services
  • Pressure boosting, fire fighting systems
  • Water supply

Technical data

  • Q max 110.0 m³/h
  • H max 160.0 m

Design Hya-Solo D FL

Fully automatic package single-pump system. The system is started and stopped as a function of pressure. Design and function as per DIN 14462.

Application pump Hya-Solo D FL

Fire-fighting systems to DIN 14462

Drive pump Hya-Solo D FL

Hya-Solo D

  • Three-phase asynchronous squirrel-cage motor
  • Efficiency class IE3
  • 220-240 V/ 380-420 V ; 380-420 V/ 660-720 V
  • IP55 enclosure
  • Thermal class F
  • DOL starting up to and including 4 kW
  • Star-delta starting for 5.5 kW and above

Hya-Solo DSV

  • KSB SuPremE IE4 motor (as per IEC/CD 60034-30 Ed. 2)
  • Three-phase motor
  • 380 V AC -10% up to 480 V AC +10%, 50/60 Hz
  • IP55 enclosure

Desing Details pump Hya-Solo D FL

Hya-Solo D

  • Fully automatic pressure booster package system
  • Membrane-type accumulator (direct-flow) to DIN 4807-5
    on the discharge side, approved for drinking water
  • Pressure gauge for pressure indication
  • Fully automatic pressure booster package system
  • Membrane-type accumulator (direct-flow) to DIN 4807-5 on the discharge side, approved for drinking water
  • Pressure gauge for pressure indication Installation type
  • Stationary installation

Fluids handled

  • Drinking water
  • Service water
  • Cooling water
  • Fluids not chemically or mechanically aggressive to the materials

Overview of technical data Hya-Solo D FL

Q (50Hz)0.0 – 110.0 (m³/h)
H (50Hz)10.0 – 160.0 (m)
Type of bearingPlain bearings
Drive frequency50 Hz
Type of driveElectric motor
Drive voltageLow voltage
Impeller material (EN standard)1.4301
Type of lubricationProduct lubrication
Max. permissible fluid temperature70.0 (°C)
Nozzle positionIn-line
Maximum operating pressure16 BAR
Pump set locationDry installed
Suction characteristicsNon-priming
Suitable for drinking waterYes
Type of connectionScrew-ended, flange
Casing material (EN standard)1.4301
Maximum inlet pressure6.0 (bar)
Minimum inlet pressure0.5 (bar)
Installation positionVertical
Main applicationsIndustry and process engineering, Water, Building services
Casing materialChrome nickel steel
Maximum discharge-side pressure16.0 (bar)
Maximum drive rating22.0 (kW)
Type of installationStationary
Maximum speed of rotation2900.0 (1/min)
Type of connectionDirect