
Main applications hyamat V
- Building services
- Fire fighting and sprinkler systems
- Pressure boosting, fire fighting systems
- Water supply
Technical data
- Q max 660.0 m³/h
- H max 160.0 m
Design hyamat v
Fully automatic package pressure booster system with 2 to 6 vertical high-pressure pumps and continuously variable speed adjustment of one pump; for fully electronic control of the required supply pressure. Design and function as per DIN 1988. Automated with BoosterControl.
Application pump hyamat v
Pressure boosting in residential buildings, hospitals, office buildings, hotels, department stores, industry, etc.
Drive pump hyamat v
Electric motor 50 Hz, 2-pole, IE3, special KSB model, for three-phase mains
Desing Details pump hyamat v
Design
▪ Fully automatic pressure booster package system
▪ Baseplate-mounted
▪ Two to six vertical high-pressure centrifugal pumps, one of them with continuously variable speed adjustment
▪ Hydraulic components made of stainless steel / brass
▪ One check valve and shut-off valves to DIN/DVGW for each
pump
▪ Anti-vibration mounts for each pump for systems with Movitec 2B, 4B, 6B, 10B, 15B
▪ Systems with level-adjustable feet with rubber pads (supplied but not fitted) for systems with Movitec 25B, 40B, 60B and 90B
▪ Membrane-type accumulator (direct-flow) to DIN 4807-5 on the discharge side, approved for drinking water
▪ Pressure gauge for pressure indication
▪ Pressure transmitter on the discharge side
▪ Design and function as per DIN EN 806-2, DIN 1988-500
Installation type
▪ Stationary installation
Overview of technical data hyamat v
| Q (50Hz) | 0.0 – 660.0 (m³/h) |
| H (50Hz) | 5.0 – 160.0 (m) |
| Type of bearing | Plain bearings |
| Drive frequency | 50 Hz |
| Type of drive | Electric motor |
| Drive voltage | Low voltage |
| Type of first impeller | Closed / Radial |
| Other impeller types | Closed / Radial |
| Impeller material (EN standard) | 1.4301 |
| Type of coupling | Direct |
| Type of lubrication | Product lubrication |
| Max. permissible fluid temperature | 70.0 (°C) |
| Nozzle position | In-line |
| Number of pumps | 6 |
| Maximum operating pressure | PN 16 |
| Pump set location | Dry installed |
| Suction characteristics | Non-priming |
| Suitable for drinking water | Yes |
| Type of connection | Screw-ended, flange |
| Type of stage casing | Stage casing with diffuser |
| UNSPSC classification | 4015150300 |
| Casing material (EN standard) | 1.4301 |
| eClass assignment | 36410101 |
| Maximum inlet pressure | 10.0 (bar) |
| Installation position | Vertical |
| Shaft seal type | Mechanical seal |
| Main applications | Building services, Water, Industry and process engineering |
| Casing material | Chrome nickel steel |
| Maximum discharge-side pressure | 16.0 (bar) |
| Maximum drive rating | 22.0 (kW) |
| Type of installation | Stationary |
| Maximum speed of rotation | 2900.0 (1/min) |
| Standby pump | Yes |
| Type of connection | Indirect and direct |



