Hyamat-K-booster-pump-ksb
Hyamat-K-booster-pump-ksb

Main applications hyamat k

  • Building services
  • Pressure boosting, fire fighting systems
  • Water supply

Technical data

  • Q max 450.0 m³/h
  • H max 160.0 m

Design hyamat k

Fully automatic package pressure booster system with 2 to 6 vertical high-pressure pumps and fully electronic control to ensure the required supply pressure, with volt-free changeover contact for general fault indication and live-zero monitoring of the connected sensors, design and function to DIN 1988. Automated with BoosterControl

Application pump hyamat k

Pressure boosting in residential buildings, hospitals, office buildings, hotels, department stores, industry, etc.

Drive pump hyamat k

  • Electric motor 50 Hz
  • 2 poles
  • Efficiency class IE3 to IEC 60034-30
  • Special KSB model
  • For three-phase mains

Desing Details pump hyamat k

Design

▪ Fully automatic pressure booster package system
▪ Baseplate-mounted
▪ Two to six vertical high-pressure centrifugal pumps
▪ Hydraulic components made of stainless steel / brass
▪ 1 check valve and 1 shut-off valve per pump set to
DIN / DVGW
▪ Discharge-side, direct-flow membrane-type accumulator, approved for drinking water
▪ Pressure gauge
▪ Pressure transmitter on the discharge side
▪ Design and function as per DIN EN 806-2
Pressure booster system with Movitec 2B, 4B, 6B, 10B and 15B
▪ Anti-vibration pads per pump Pressure booster system with Movitec 25B, 40B, 60B and 90B
▪ Level-adjustable feet and rubber pads (supplied but not fitted)

Installation

▪ Stationary dry installation

Overview of technical data hyamat k

Q (50Hz)0.0 – 450.0 (m³/h)
H (50Hz)6.0 – 160.0 (m)
Type of bearingBall and plain bearings
Drive frequency50 Hz
Type of driveElectric motor
Drive voltageLow voltage
Type of first impellerClosed / Radial
Other impeller typesClosed / Radial
Impeller material (EN standard)1.4301
Type of installationLong-coupled
Type of couplingDirect
Type of lubricationProduct lubrication
Discharge casing material (EN standard)1.4301
Max. permissible fluid temperature70.0 (°C)
Nozzle positionIn-line
Number of pumps6
Maximum operating pressurePN 16
Pump set locationDry installed
Stage casing material (EN standard)1.4301
Suction casing material (EN standard)1.4301
Suction characteristicsNon-priming
Suitable for drinking waterYes
Type of connectionScrew-ended, flange
Type of stage casingStage casing with diffuser
UNSPSC classification4015150300
Casing material (EN standard)1.4301
eClass assignment36410101, 00000000
Maximum inlet pressure10.0 (bar)
Installation positionVertical
Shaft seal typeMechanical seal
Main applicationsIndustry and process engineering, Water, Building services
Casing materialChrome nickel steel
Maximum discharge-side pressure16.0 (bar)
Maximum drive rating22.0 (kW)
Type of installationStationary
Maximum speed of rotation2900.0 (1/min)
Standby pumpYes
Type of connectionDirect