Main applications hya-solo dsv
- Building services
- Fire fighting and sprinkler systems
- Pressure boosting, fire fighting systems
- Water supply
Technical data
- Q max 65.0 m³/h
- H max 150.0 m
Design hya-solo dsv
Fully automatic variable speed package single-pump system with PumpDrive 2 / PumpDrive 2 Eco. The system is started as a function of pressure and stopped as a function of flow.
Application pump hya-solo dsv
Water supply systems for residential and office buildings, irrigation and spray irrigation, rainwater harvesting and service water supply systems in trade and industry.
Drive pump hya-solo dsv
- Three-phase asynchronous squirrel-cage motor
- Efficiency class IE3 to IEC 60034-30
- 220 – 240 V / 380 – 420 V, 380 – 420 V / 660 – 720 V
- Enclosure IP55
- Thermal class F
- DOL starting up to and including 4 kW
- Star-delta starting ≥ 5.5 kW
Desing Details pump hya solo dsv
Design
▪ Fully automatic pressure booster package system
▪ Discharge-side, direct-flow membrane-type accumulator, approved for drinking water
▪ Pressure gauge
Installation
▪ Stationary dry installation
Fluids handled
▪ Drinking water
▪ Service water
▪ Cooling water
▪ Fluids not chemically or mechanically aggressive to the materials
Automation
▪ Control unit for pressure-controlled starting and stopping
▪ Control unit (IP54 enclosure)
▪ LEDs indicate faults and lack of water
▪ Motor protection switch
▪ Manual-0-automatic selector switch
▪ Timer for daily operation check run
▪ Terminal strip with markings for all connections
▪ Volt-free contacts for operation, fault, lack of water
▪ Lockable master switch (repair switch)
Overview of technical data hya-solo dsv
Q (50Hz) | 0.0 – 65.0 (m³/h) |
H (50Hz) | 10.0 – 150.0 (m) |
Barrel casing | Yes |
Type of bearing | Plain bearings |
Drive frequency | 50 Hz |
Type of drive | Electric motor |
Drive voltage | Low voltage |
Type of first impeller | Closed |
Impeller material (EN standard) | 1.4301 |
Type of installation | Long-coupled |
Type of coupling | Direct |
Type of lubrication | Product lubrication |
Max. permissible fluid temperature | 70.0 (°C) |
Nozzle position | In-line |
Number of pumps | 1 |
Maximum operating pressure | PN 16 |
Pump set location | Dry installed |
Shaft material (EN standard) | 1.4305 |
Stage casing material (EN standard) | 1.4301 |
Suction casing material (EN standard) | 1.4301 |
Suction characteristics | Non-priming |
Suitable for drinking water | Yes |
Type of connection | Screw-ended, flange |
Type of stage casing | Stage casing with diffuser |
UNSPSC classification | 4015150300 |
Casing material (EN standard) | 1.4301 |
eClass assignment | 36410101 |
Maximum inlet pressure | 6.0 (bar) |
Minimum inlet pressure | 0.5 (bar) |
Installation position | Vertical |
Shaft seal type | Mechanical seal |
Main applications | Industry and process engineering, Water, Building services |
Casing material | Chrome nickel steel |
Maximum discharge-side pressure | 16.0 (bar) |
Maximum drive rating | 22.0 (kW) |
Type of installation | Stationary |
Maximum speed of rotation | 2900.0 (1/min) |
Type of connection | Direct |
Operating mode | Variable |