Main applications Hya-Solo D FL Compact
- Main applications
- Pressure boosting
- Pressure boosting, fire fighting systems
- Water
- Watertransport
Technical data
- Q max 36.0 m³/h
- H max 160.0 m
Design Hya-Solo D FL Compact
Fully automatic ready-to-connect break tank package booster set for fire fighting, comprising a single-pump system and break tank. The system is started and stopped as a function of pressure. Design and function as per DIN 14462.
Application pump Hya-Solo D FL Compact
Fire-fighting systems to DIN 14462
Drive pump Hya-Solo D FL Compact
- Three-phase asynchronous motor
- 380 / 420 V, 50 Hz
- 2 poles
- Enclosure IP55
- Efficiency class IE3 to IEC 60034-30
- Soft starter
- Pressure-controlled starting and flow-controlled stopping
Desing Details pump Hya-Solo D FL Compact
- Fully automatic break tank package booster set for fire fighting to EN 1717
- Baseplate-mounted
- Modular design (comprising 3 modules):
– Control cabinet with hydraulic unit (pump set, valves, piping, pressure switch2) and temperature sensor2))
– Baseplate
– Tank with inlet device and flushing device, overflow monitoring and dry running monitoring3) - Vibration damping
Fluids handled
- Fire-fighting water
- Liquids not containing aggressive, abrasive or solid substances
Overview of technical data Hya-Solo D FL Compact
Q (50Hz) | 0.0 – 36.0 (m³/h) |
H (50Hz) | 30.0 – 160.0 (m) |
Drive | Electric motor |
Connection to power supply | 400 V, 3~ |
Max. permissible fluid temperature | 70.0 (°C) |
Maximum operating pressure | 16 BAR |
Suitable for drinking water | Yes |
Maximum inlet pressure | 0.5 (bar) |
Minimum inlet pressure | 5.0 (bar) |
Maximum discharge-side pressure | 16.0 (bar) |
Maximum speed of rotation | 2900.0 (1/min) |
Standby pump | Yes |